  1. Inspect your ATC board for LED lights that are illuminated. If you have no lights at all, move to the step.

  2. If you have lights on your board but still no communication, ensure all wires are properly seated and secured in the terminals on the ATC board itself and try and reseat the connector

  3. Check for 48 Vdc across wires 204 200 and 205 201 at the ATC control board.

...

...

  1. If you have voltage at the board but no lights, remove components from the board one at a time, (excluding the incoming power) to vet if a component is shorting the board.

  2. If you do not have +48 Vdc across wires 204 200 and 205201, move to the 48V Power Supply in the machine column. Measure for 48V DC on the power supply from the V+ and V- wires from the ATC.

...

  1. Your ATC board should show the following LEDs lit if it has +48 Vdc at wires 503 204 and 504 205 at the ATC control board and is successfully talking to PathPilot.

...

  1. If you have +48 Vdc at wires 503 204 and 504 205 at the ATC control board but no lights on the board, contact Tormach Tech Supportremove components from the board one at a time, (excluding the incoming power) to vet if a component is shorting the board.

  2. If you do not have +48 Vdc across wires 503 204 and 504205, move to the 48V Power Supply in the machine column. Measure for 48V DC on the power supply from the V+ and V- wires from the ATC.

  3. If you continue to experience the check fuses and cabling error, contact Tormach Tech Support.

...